You are on the Pilz international website
Please select a language or switch to a country
Choose your country to get national content
PSS u2 P0 F/S PN2
Phase-out article
Save basket
Create a new order or get an individual offer
Select intended use
Head module for PSS u2 in remote I/O system, failsafe and standard, 2 RJ45 female connectors, PROFINET with PROFIsafe profile, Conformance Class C (CC-C), IRT/RT, Shared Device, integrated supply voltage for connecting module supply and periphery supply, potential isolation, connection for functional earth, slot for microSD card Important information: This item is at the end of the product lifecycle and therefore will no longer be available in the foreseeable future. Please get in touch with your PILZ contact to find a suitable alternative or successor product.
| Approval |
CE
UKCA cULus Listed TÜV EAC (Eurasian) |
| Application range | Standard/failsafe |
| Purpose of U1 | Module supply |
| Supply voltage (V) |
24
24 |
| Type of supply voltage U1 | DC |
| Power consumption DC | 28.8 |
| Potential isolation U1 | Yes |
| Purpose of U2 | Periphery supply |
| Supply voltage U2 |
24
24 |
| Type of supply voltage U2 | DC |
| Tolerance of U2 | -30 %/+25 % |
| Potential isolation U2 | Yes |
| Plug-in memory | µSD card |
| Settable trans.rate PROFINET | 100 MBit/s |
| Trans. rate setting PROFINET | Automatic |
| PROFINET certification | PNO |
| PROFINET manufacturer ID | 092Fh |
| Connector type PROFINET i/f | RJ45 |
| PROFINET type | IO device |
| Cycle time PROFINET (RT) | 1 ... 512 ms |
| Cycle time PROFINET (IRT) | 1 ... 16 ms |
| Climatic suitability to ... |
EN 60068-2-30
EN 60068-2-2 EN 60068-2-1 EN 60068-2-78 EN 60068-2-14 |
| Ambient temperature standard | EN 60068-2-14 |
| Ambient temperature |
0
60 |
| Storage temperature standard | EN 60068-2-1/-2 |
| Climatic suitability standard | EN 60068-2-78 |
| Humidity rating | 93 % r. h. at 40 °C |
| Condensation permitted? | Not permitted |
| Perm. operating height ASL | 2000 m |
| EMC to standard ... | EN 61131-2 (Zone B) |
| Vibration to standard ... | EN 60068-2-6 |
| Acc. shock to standard1 | 150 m/s² |
| Clearance & creepage dist. to |
EN 61131-2
UL/IEC 61010-2-201 |
| Overvoltage category | II |
| Pollution degree clear.&creep. | 2 |
| Protection type, mounting | |
| Protection type, housing | IP20 |
| Potential isolation 1 between | UB and periphery supply |
| Type of potential isolation 1 | Functional insulation |
| Potential isolation 2 between | UB and module supply |
| Type of potential isolation 2 | Functional insulation |
| Potential isolation 3 between | Periphery and module supply |
| Type of potential isolation 3 | Functional insulation |
| Potential isolation 4 between | Module supply and PROFINET |
| Type of potential isolation 4 | Functional insulation |
| Housing material lower section | PPE |
| Housing material upper part | PC |
| Connection terminal | Spring-loaded terminal |
| Terminal style | plug-in |
| Height dimension | 110.1 |
| Width dimension | 64.1 |
| Depth dimension | 94.7 |
| Net weight | 240 |
| Gross weight | 260 |
| RoHS directive |
2011/65/EU
2015/863/EU |
| RoHS conformity | yes |
| RoHS exceptions | yes |
| RoHS except.s acc. to direct. | 7a |
| REACh compliance | contains min. 1 SVHC-substance |
| REACh included substances | Lead |
| %-part of the pollutant | > 0,1 |
| CAS No. | 7439-92-1 |
| SCIP entry available | yes |
| WEEE classification (08/2018) | 5 devices (feed size < 50cm) |
| ECLASS version | ECLASS-13 |
| ECLASS Reference Feature | 27242608 |
| ETIM Version | ETIM-9.0 |
| ETIM Reference Group | EG000024 |
| ETIM Reference Feature | EC001604 |
| UNSPSC 25 | 39122331 |
| GTIN | 4046548071917 |
| Volume | 0.805 dm3 |
| Harmonized System Code | 85389091 |
| Type of tariff number | TARIC |
| Use of customs tariff number |
Ausfuhr
Einfuhr |
| Quantity per packaging unit | 1 |
Optional accessories