PSSu H FS2 SN SD-T

Product ID: 314087
GTIN: 4046548088229
PSSu, head module with increased performance, control system PSSu I/O, failsafe and standard, PL e, SIL CL 3, 2 RJ45 ports, SafetyNET p RTFN, SD card 512 MB, for increased environmental requirements.

Item

Save basket

Create a new order or get an individual offer

Select intended use

Approval CE  
UKCA  
cULus Listed  
TÜV  
EAC (Eurasian)  
Application range Standard/Fail-safe  
 
Purpose of U1 Module Supply  
Supply voltage (V) 24  
Type of supply voltage U1 DC  
Power consumption DC 17  
Purpose of U2 Periphery Supply  
Supply voltage U2 24  
Type of supply voltage U2 DC  
Tolerance of U2 -30 %/+25 %  
Pot. isolation UINT1 to U2 P_UINT1_5V_U_2_POT_TRENN_2000 V  
Purpose of UINT1 int. Systemspannung  
Type of UINT1 DC  
Tolerance of UINT1 -2 %/+3 %  
Max. curr. contin. oper. UINT1 2  
Bridge U-interrupt UINT1 stan. EN61131-2  
UINT1 short circuit proof ja  
IEC 61131 programming nein  
Multi programming nein  
Non-volatile variables nein  
Time deviation +/- 10s/Tag  
RAM 256 MB  
Plug-in memory SD-Karte  
Connector type Safetynet i/f RJ45  
Safetynet transmission rate 100 MBit/s  
Setting SafetyNet trans.rate automatisch  
SafetyNET p cycle time 2 ... 60 000 ms  
Climatic suitability to ... EN 60068-2-30  
EN 60068-2-2  
EN 60068-2-1  
EN 60068-2-78  
EN 60068-2-14  
Ambient temperature -40  
Climatic suitability standard EN 60068-2-78  
Humidity rating 93 % r. F. bei 40 °C  
Condensation permitted? EN 60068-2-30  
kurzzeitig  
Perm. operating height ASL 5000 m  
EMC to standard ... EN 61000-6-2  
EN 61000-6-4  
EN 61131-2 (Zone B)  
Vibration to standard ... EN 60068-2-6  
Broad band noise to EN 60068-2-64  
Acc. shock to standard1 150 m/s²  
Acc. shock to standard2
Clearance & creepage dist. to EN 61131-2  
Overvoltage category II  
Pollution degree clear.&creep. 2  
Protection type, mounting IP54  
Protection type, housing IP20  
Potential isolation 1 between Periphery und Module Supply  
Type of potential isolation 1 Funktionsisolierung  
Potential isolation 2 between Periphery Supply und Systemsp.  
Type of potential isolation 2 Funktionsisolierung  
Housing material lower section PC  
Connection terminal Federkraftklemme  
Schraubklemme  
Terminal style steckbar  
Flex. cond. c/s AWG info 24 - 12 AWG  
Height dimension 125.6  
Width dimension 130  
Depth dimension 83.7  
Net weight 350  
Gross weight 390  
 
RoHS directive 2011/65/EU  
2015/863/EU  
RoHS conformity yes  
RoHS exceptions yes  
RoHS except.s acc. to direct. 7a  
7c I  
REACh compliance contains min. 1 SVHC-substance  
REACh included substances Lead  
%-part of the pollutant > 0,1  
CAS No. 7439-92-1  
SCIP entry available yes  
WEEE classification (08/2018) 5 devices (feed size < 50cm)  
 
ECLASS version ECLASS-13  
ECLASS Reference Feature 27242207  
ETIM Version ETIM-9.0  
ETIM Reference Group EG000024  
ETIM Reference Feature EC000236  
UNSPSC 25 39122331  
GTIN 4046548088229  
Volume 1.456  dm3
Harmonized System Code 85371091  
Type of tariff number TARIC  
Use of customs tariff number Ausfuhr  
Einfuhr  
Quantity per packaging unit 1  
 

Optional accessories

Stripping Tool
Stripping Tool 380070
Tool for fast and multi-stage stripping of Ethernet and SafetyNET p cables, PU 1 set.
M12 con., straight, male, 4 pin, D
M12 con., straight, male, 4 pin, D 380316
Plug-in connector, 4-pin, connector straight M12, D-coded, screw connection, material threaded ring: Zinc die casting,nickel-plated, cable screw connection Pg9, outer cable diameter 6-8mm

Obligatory accessories

PSSu A Con 1/4 S (2 pcs.)
PSSu A Con 1/4 S (2 pcs.) 313110
PSSu, connector set for supply voltage, 1-row, 4-pin, screw connection, PU 2 connectors.
PSSu A Con 2/8 C (2 pcs.)
PSSu A Con 2/8 C (2 pcs.) 313111
PSSu, connector set for supply voltage, 2-row, 8-pin, spring-loaded connection, PU 2 connectors.